SR 100HL – AC/DC Power Supply 100W with Comms

Brand: HELIOS POWER SOLUTIONS

SKU: HPS-PS-STANDALONE-SR100HL
This product is available globally.
  • This product is not available until further notice. Please contact our sales engineers for alternatives. 

Description

SR100HL

100W – AC/DC Power Supply / Battery Charger

The SR100HL range is designed for use as a reliable and stable AC to DC power supply, or float charger for lead-acid batteries. Note that for float charging the output voltage must be set to approximately 15% above the nominal battery voltage models. This is done as the default voltage for the 12V model but must be specified at time of order for all higher voltage models.

Applications

  • Security – Access Control
  • Industrial Processes Switching Protection
  • SCADA
  • Radio Repeaters – Remote Sites

Points of Difference

  • Ideal for standby float charging of lead-acid batteries
  • Constant current limit and Precise voltage control
  • Temperature compensation option
  • Efficient modern “current mode”
  • Relay Alarms Output
  • Suitable for parallel operation
  • Rugged design and construction for long life and   challenging environments

Optional Features

  • American Input Voltage 110 VAC ( 88 – 135 VAC)
  • Communication Port ( RS232 ASCII – SR485 – MODBUS Serial – SNMP , webpages)
  • Digital Input/Outputs: Customizable 3 digital inputs & 1 digital output.
  • Mounting: DIN rail, 19″ Rack Mount  with V/I meter available, Wall mount
  • N+1 redundancy
  • Boost Charger
  • Conformal coating for harsh environments

SR100HL – 100 w – Power Supply/Battery Charger with optional comms

SERIES TABLE

MODELSPower SupplyBattery Charger*Adjustable range (V)
Output Volts (factory default)Output Current (A) (continuous)Output  Volts* (Charging)Output Current (A) (Charging)
SR100HL1213.87.313.87.311-14
SR100HL24244.227.63.622-28
SR100HL30303.334.52.927-33
SR100HL36362.841.42.634-43
SR100HL48482.155.21.845-57

SPECIFICATIONS TABLE

Output power100W (0-50°C )
Input Voltage180V – 264VAC 45-65Hz
Output Voltages13.8V, 24, 30V, 36V, 48 VDC
Other voltages by request
Voltage Adj. Range85% – 105% of Vout
Frequency45-65Hz
Overcurrent protectionConstant current limit under overload and short circuit conditions
IsolationInput – earth – 2.5KVdc
Output – earth – 500Vdc
Efficiency> 85%
Inrush Current< 30A , 1.8ms
Operating temperature-20  to 50 °C ambient at full load
Humidity0 – 95% relative humidity non – condensing
CoolingNatural convection
LED IndicationGreen: DC OK
Green: Power OK
Alarms RelayForm C contacts changeover, rated 30VDC,2A/110VDC,0.3A/125VAC,0.5A
DC Hight ()
POWER  (main fails, PSU fail)
DC Low  ()
Line Regulation<0.04% over input range
Load Regulation<0.5% open circuit to 100% load
Noise<0.3%
Transient response200mV over/undershoot,
Load step 20-100%, 400us settling time
Hold-up time15-20 ms (nom-max. Vin) without battery

OPTIONAL FEATURES

Optional Input Voltage88 – 132 VAC
Communication PortRS232 (ASCII)
RS485 (ASCII)
Modbus RTU
SNMP, Webpages
Inputs/OutputsCustomizable 3 Digital Inputs and 1 Digital Output
Temp. CompensationTemperature sensor on 1.7m lead with adhesive pad: -4mV / °C / cell ±10%
MountingDIN Rail
Standalone
19”Rack Mount – Optional V/I meter for subrack : SR-Meter
N+1 RedundancyUsing 2 chargers each with its own battery
Boost ChargerCustomizable feature on

MODELS REPLACED BY SR100HL

Modbus & SNMP Downloads

SR Series – Comms Downloads