BAT-0400-M-1U Military Grade Expansion Battery Pack

Brand: Synqor

SKU: BAT-0400-M-1U
Note: Serviced regions include Australia, New Zealand, Middle East, Asia.
  • Sealed, weather-proof, shock-proof construction
  • >16.5 minute run-time at full power
  • 1250W continuous output power
  • Full discharge: -40 °C to +55 °C
  • Low weight: 11.8 lbs.
  • <1U high unit (15.00” x 10.89” x 1.46”)

Description

BAT-0400-M-1U

Military Grade Expansion Battery Pack | -40 °C to +55 °C Operating Temperature

The BAT-0400-H-1U Series is a military-grade expansion battery pack that uses lithium polymer batteries and highly efficient power electronic circuitry to achieve a high power level and battery run-time in a low-profile, low-weight, rack-mountable package. It is designed specifically for use with SynQor UPS-1250, UPS-1500 and UPS-3000 series uninterruptible power supplies (UPS). It is designed for the extreme environmental and demanding electrical conditions of Military/Aerospace applications.

The pack cannot be used as a standalone battery. Multiple layers of circuit protection are implemented internal to the battery pack. Features include heater resistors for operating down to -40°C ambient, and internal hardware protection and status monitoring.

The BAT-0400-M pack provides cold-start operation down to -40°C. A cold-start is an enable of the UPS using only battery power, with no input power available. Below -20°C, following a cold-start enable command from the user, the BAT-0400 will pre-heat itself to operational temperature, then enable the UPS output.

From a start with the battery pack soaked at -40°C, the cold-start pre-heat takes 3.5 minutes. The pre-heat terminates based on internal cell temperatures, so a cold-start from a temperature warmer than -40°C will take less than 3.5 minutes. Although operation at full output load requires a full pre-heat sequence, the user can optionally set the pre-heat to terminate early if the output load is known to be less than full load.

Specification Compliance

When installed inside a UPS-1250/1500/3000, the system is designed to meet:

  • MIL-STD-1399-300B – Interface Std for Shipboard Systems
  • MIL-STD-810G – Environmental Engineering Considerations
  • MIL-STD-461F – Electromagnetic Interference
  • MIL-STD-704F – Aircraft Electrical Power Characteristics
  • MIL-STD-1275D – Vehicle Electrical Power Characteristic

Compatible with UPS-1250, UPS-1500 & UPS-3000 models

Additional information

Weight 5.35239 kg

LITHIUM-POLYMER BATTERY PACK MONITORING FEATURES

  • Total Pack Output Voltage
  • Internal Pack Voltage
  • Total Voltage of Series-Connected Cells
  • Individual Cell Voltages
  • Status of Charge and Discharge Protection Switches
  • Total Pack Output Current
  • Internal Pack Current
  • Cell Temperatures
  • PCB Temperatures

LITHIUM-POLYMER BATTERY PACK PROTECTION FEATURES

Discharge Protection

  • Cell Under-Voltage Lockout, Software
  • Cell Under-Voltage Lockout, Hardware
  • Cell Under-Voltage Lockout Timer
  • Excessive String Current
  • String Short-Circuit Current
  • Excessive Pack Current
  • Detection of UPS Chassis Installation
  • Cell Temperature Too Hot for Discharge
  • Cell Temperature Too Cold for Discharge
  • PCB Temperature Too High

Charge Protection

  • Cell Over-Voltage Lockout, Software
  • Cell Over-Voltage Lockout, Hardware
  • Cell Over-Voltage Lockout Timer
  • Excessive Charging Current
  • Total String Voltage Too Low
  • Detection of UPS Chassis Installation
  • Cell Temperature Too Hot for Charging
  • Cell Temperature Too Cold for Charging
  • PCB Temperature Too High

String Heater Overrides

  • Timeout
  • PCB Temperature
  • Measured Pack Voltage
  • Any Cell Temperature