TC-1100 Industrial AC UPS 1100VA/1100W

Brand: HELIOS POWER SOLUTIONS

SKU: HPS-AC-UPS-OUTDOOR-TC1100-1100VA
This product is available globally.
  • Wide operating temperature range -37 °C to 74°C and no derating
  • Six Fully Programmable Dry Contacts
  • Pure Sine Wave output voltage 220/230/240VAC
  • Local and remote monitoring and control via RS232 port and Ethernet SNMP interface / Modbus on TCP-IP (optional)
  • Compliant to Transportation Electrical Equipment Specifications (TEES) – Suitable for outdoor applications

Product Range

SKU Type AC UPS Max Load AC UPS
TC-1100HTLine Interactive1100W

For additional accessories such a rack mount kit and SNMP or Modbus Network interface card please contact our sales engineers

Description

TC-1100 Industrial AC UPS 1100VA/1100W

Rack Mount Uninterruptible Power Supply for High Temperature & Outdoor Applications

The TC UPS range went through several practical tests and confirmed its industrial grade for protection. It meets TEES ( Transportation Electrical Equipment Specifications) and can be installed in outdoor cabinets.

TC Series has an automatic voltage regulator (AVR) function, which converts the unstable voltage into safe and stable for electronic equipment. It has an LCD screen that displays battery voltage and battery temperature, the system detects battery temperature and automatically adjusts the voltage to increase the battery life. SNMP card is optional and was designed to support high-temperature environments as well.

Main Features

  • Rock mounting design
  • Wide operating temperature range -37 °C to 74°C and no derating
  • Remote on / off control
  • Six Fully Programmable Dry Contacts
  • Pure Sine Wave output voltage 220/230/240VAC
  • Local and remote monitoring and control via RS232 port and Ethernet SNMP interface (optional)
  • Compliant to to Transportation Electrical Equipment Specifications (TEES)
  • Build- in AVR Function

Applications:

  • Outdoor base stations
  • Environmental monitoring stations
  • Traffic signal centers
  • Outdoor observation centers
  • Solar farms CCTV systems and PV monitoring and control systems

Additional information

Weight 13 kg
Dimensions 254 × 432 × 88.6 mm

SPECIFICATIONS TABLE

UPS
ModelTC- 1100
Capacity(VA)1100 VA
Capacity(Watts)1100 W
INPUT
Voltage120 Vac ±25% – 220 / 230 / 240Vac ±25%
Frequency120Vac 60Hz – 220 / 230 / 240Vac 50/60Hz
OUTPUT
WaveformPure Sine Wave
Voltage120Vac or 220 / 230 / 240Vac
Frequency50 / 60 Hz ± 0.5 Hz
Transfer TimeNormal Mode (Max)12 ms
Transfer TimeGenerator Mode (Max)25 ms
AC Input & Output ConnectorsTerminal block, Anderson PP45 quick connector, IEC socket
PROTECTION
Full ProtectionOverload, Breaker
MANAGEMENT & COMMUNICATION
Communication PortRS232, USB(B- Type), SNMPCard(Optional)
BATTERY
String Voltage24/48 VDC
TypeLead- acid battery
Max Charge Current10A
INDICATORS
LCD Display4 line multi- function LCD
LED DisplayOutput status, alarm, fault LED
ENVIRONMENT
Operating Temperature  – 37 ~ 74°C
Operating Humidity  0 ~ 95 % RH (Non- condensing)
Audible NoiseLess than 60dB
PHYSICALY
Dimensions (WxDxH)(mm) 432 x 254 x 88.6
Weight (kgs)13