Current rating | 1Ph: 125A max 3Ph: 63A max |
Voltage rating | All region-specific voltages ±10% |
Type | Single phase, 3-Phase/3-Pole or 3-Phase/4-Pole |
Frequency | 50Hz and 60Hz, ±10% – Auto detection |
Transfer type | Break-Before-Make zero current transfer by Thyristors / SCR |
Synchronous break time | <1ms – up to ¼ cycle |
MTBF | >800,000 hours |
Maintenance bypass | 3-position overlapping, no-break CAM switch |
Isolation | Incoming sources isolator switches |
Display | Bi-colour LED mimic decal |
Interface | Preferred supply selection, Source transfer selection and Alarm cancel button |
Contact | 2 Self wetting transfer control inputs 5 Pre-defined Voltage free change-over status indicators, Form C |
Ethernet | HTTP, SNMP, MODBUS TCP, Email & NTP – Modbus RTU Optional |
Input termination | Lugged fixed wiring to M6/M8 terminals via glands |
Output termination | Lugged fixed wiring to M6/M8 terminals via glands |
Dimensions H x W x D | H600 x W400 x D190 mm |
Weight | 34kg |
Temperature | 0 – 55°C |
IP rating | IP54 |
Detection | Digital: <1ms |
Asynchronous break time | 0ms, 10ms, 50ms or Vt proportional, 0° to 180° |
Loading | 0 – 100% @55°C ambient |
Device ratings | 134A RMS, 1600V, 2kA 1 cycle |
Overload @55°C ambient | 110% for 10min 125% for 2min 150% for 60s 200% for 30s 400% for 0.1s 2kA for 1 cycle |
Fault current setting | 300% peak with load fault transfer inhibit |
Safe install environment | 20kA, 100A/200A internally fused |
Protection | 100A/200A fuses – BS88/FE100 |
Power factor | No practical limit |
Max THDV | 10% – Max allowable source voltage distortion |
Crest factor | 3 : 1 |
dV/dt max | 800V/μs |
Cooling | Natural |
Humidity @40°C ambient | 5 – 95% non-condensing |
Regulatory approvals | IEC 62310-1,2,3 – IEC 60950 – IEC 61000-6-1,2,3,4 – CE – RCM – UL Capable – RoHS |
Standard warranty | 24 months offsite repair or replacement policy |