  • Input voltage: 12Vdc nominal (10.8V to 16V continuous)
  • Output voltage: 12Vdc (+/- 7% adjustable)
  • Output current: 5A
  • Convection cooled & ruggedised, fully encapsulated.
  • EMC hardened for “dirty” electrical environments.
  • Reliable and durable with field-proven MTBF (720,000hrs)

Datasheets

48-12Vdc 5A 60W DC-DC Converter – DIN Rail / Panel Mount – APK60-4812

48-12Vdc 5A 60W DC-DC Converter – DIN Rail / Panel Mount – APK60-4812

Description

High reliability 60W industrial DC-DC converter.

Features

  • Input voltage: 48Vdc nominal (42V to 64V continuous)
  • Output voltage: 12Vdc (+/- 7% adjustable)
  • Output current: 5A
  • Convection cooled & ruggedised, fully encapsulated.
  • EMC hardened for “dirty” electrical environments.
  • Reliable and durable with field-proven MTBF (720,000hrs)
  • Simple installation with top-down mounting and pluggable I/O connections, DIN rail ready.

 

Specifications Table

 

Input
Reverse Polarity ProtectionBlow input fuse
(see recommended input fusing above)
Input Surge, Transient, and Immunity1.5kW transorb protected
Output
Setup Accuracybetter than 4%
Input Adjustment+/- 10% typical
Line & Load Regulationbetter than 0.25%
Noise & Ripple (20MHz BW)better than 1% (<100mVp-p 5V models)
Efficiency88% (typical)
Current Limit120% Irated (@90%Vnominal)
Overload ProtectionConstant Current / Hiccup Mode
Mechanical
Dimensions100(W) x 65(H) x 18(D)mm
Enclosure / CasingBlack anodised aluminium extrusion
Weight0.18kg
Isolation
Input to Output500Vdc
Input to Chassis500Vdc
Output to Chassis500Vdc
Operating Conditions
Operating Temperature max (no derating)
Standalone Free Air Convection Cooling55°C Tamb
Chassis Conduction Cooling90°C Tchassis
Over-Temperature Protection100°C Tchassis (auto-recovery)
MTBF (Gm,Tamb=25°C)720,000hrs
(designed to meet MIL-SPEC 217K)
Shock and VibrationFully Encapsulated Designed to Meet
MIL-STD 810E & IEC61373
Relative Humidity95%
Power-On IndicationGreen LED (on output side panel)
Input & Output Mating Connectors2.5mm2 Screw Terminal Block
Options
Adjustable Output-adj (+/-7% typical via pot)