| Current rating | 1Ph: 125A max 3Ph: 63A max | 
| Voltage rating | All region-specific voltages ±10% | 
| Type | Single phase, 3-Phase/3-Pole or 3-Phase/4-Pole | 
| Frequency | 50Hz and 60Hz, ±10% – Auto detection | 
| Transfer type | Break-Before-Make zero current transfer by Thyristors / SCR | 
| Synchronous break time | <1ms – up to ¼ cycle | 
| MTBF | >800,000 hours | 
| Maintenance bypass | 3-position overlapping, no-break CAM switch | 
| Isolation | Incoming sources isolator switches | 
| Display | Bi-colour LED mimic decal | 
| Interface | Preferred supply selection, Source transfer selection and Alarm cancel button | 
| Contact | 2 Self wetting transfer control inputs 5 Pre-defined Voltage free change-over status indicators, Form C
 | 
| Ethernet | HTTP, SNMP, MODBUS TCP, Email & NTP – Modbus RTU Optional | 
| Input termination | Lugged fixed wiring to M6/M8 terminals via glands | 
| Output termination | Lugged fixed wiring to M6/M8 terminals via glands | 
| Dimensions H x W x D | H600 x W400 x D190 mm | 
| Weight | 34kg | 
| Temperature | 0 – 55°C | 
| IP rating | IP54 | 
| Detection | Digital: <1ms | 
| Asynchronous break time | 0ms, 10ms, 50ms or Vt proportional, 0° to 180° | 
| Loading | 0 – 100% @55°C ambient | 
| Device ratings | 134A RMS, 1600V, 2kA 1 cycle | 
| Overload @55°C ambient | 110% for 10min 125% for 2min
 150%  for 60s
 200% for 30s
 400% for 0.1s 2kA for 1 cycle
 | 
| Fault current setting | 300% peak with load fault transfer inhibit | 
| Safe install environment | 20kA, 100A/200A internally fused | 
| Protection | 100A/200A fuses – BS88/FE100 | 
| Power factor | No practical limit | 
| Max THDV | 10% – Max allowable source voltage distortion | 
| Crest factor | 3 : 1 | 
| dV/dt max | 800V/μs | 
| Cooling | Natural | 
| Humidity @40°C ambient | 5 – 95% non-condensing | 
| Regulatory approvals | IEC 62310-1,2,3 – IEC 60950 – IEC 61000-6-1,2,3,4 – CE – RCM – UL Capable – RoHS | 
| Standard warranty | 24 months offsite repair or replacement policy |