Military Field-Grade 3-Phase – 1-Phase AC Converter – MAC-4000-1U

Brand: Synqor

SKU: MAC-4000-1U
This product is available globally.
  • Single-Phase 4000 W / 5000 VA Output
  • Surge-Rated for 5250 W / 6500 VA Transient (15 s)
  • 115 Vrms L-N, 230 Vrms L-N 50 Hz, 60 Hz, or 400 Hz Output Options
  • 90% Full Load Efficiency

Description

SynQor’s Military Field-Grade AC Phase/Frequency Changer units are designed for the extreme environmental and demanding electrical conditions of Military/Aerospace applications. SynQor’s MAC incorporates field proven high efficiency designs and rugged packaging technologies. This MAC will accept a 3-Phase AC input and change it to a well-conditioned Single-Phase AC output using a two-stage DC link isolated topology. It is designed to comply with a wide range of military standards. Options include a selection of output voltage amplitudes, frequencies and an electronic breaker on the AC output to permit fault-tolerant parallel operation for higher power and/or N+M redundant systems.

Features

  • Sealed, weather-proof, shock-proof construction
  • Two-stage, DC link isolated topology
  • 4000 W (5000 VA) output power; 15 s transient to 5250 W (6500 VA)
  • Full power operation: -40 °C to +55 °C
  • 3-Phase 360-528 Vrms L-L Δ input (draws balanced currents)
  • 47-65 Hz input frequency range
  • Pure sinusoidal AC output voltage
  • Handles 0.0—1.0 power factor loads and non-linear loads
  • Up to 32 units can be combined for higher power, higher voltage, or a 3-Phase AC output
  • Capable of N+M redundancy with optional “AC Output Electronic Breaker” (R option) and the appropriate configuration cable
  • User I/O and Configuration signal ports
  • Battle Mode for over-temperature events
  • 1U high rack mount unit (17.00”W x 22.42”D x 1.73”H)
  • Low weight: 33 lbs.

Specification Compliance

MAC-4000 units are designed to meet:

  • MIL-STD-1399-300B – Interface Std for Shipboard Systems
  • MIL-STD-810G – Environmental Engineering Considerations
  • MIL-STD-461F – Electromagnetic Interface

In-Line Manufacturing Process

  • AS9100 and ISO 9001 certified facility
  • Full component traceability

Options

  • 115 Vrms or 230 Vrms AC output
  • 50 Hz, 60 Hz, or 400 Hz AC output (software selectable)
  • Shipboard version with floating output neutral wire
  • N+1 Redundancy