MIL-SPEC Approved Dual Bus DC Distribution Panel 160A

Brand: HELIOS POWER SOLUTIONS

SKU: ICT200DB-12IRC/MIL
This product is available globally.
  • 200A peak system current rating (100A per bus)
  • Six load outputs per bus
  • High-quality, reliable hydraulic/magnetic breakers support 12V, 24V and 48VDC systems (breakers sold separately)
  • -30 to +60C operating temperature range
  • Network Watchdog feature will ping a pre-determined I.P. address and power-cycle connected device if not answered

Description

MIL-SPEC DC Distribution Panel

Smart – 1U Rack Mount Dual DC Distribution for Military Use

The ICT200DB-12IRC/MIL dual bus DC load distribution panel has been designed and engineered to meet the challenging MIL-STD-810G standard for harsh environmental and battlefield conditions. This design has been tested and verified for military use.

The ICT200DB-12IRC/MIL provides independent dual bus capability for 12V, 24V or 48V DC systems. Each bus is rated at 100 Amps and provides six breakers protected outputs. On board TCP/IP capability provides customizable remote monitoring as well as remote shutdown and power cycling of individual outputs. Five digital input contacts are provided for site monitoring sensors such as door, smoke, and water detection. Each input can be custom labelled in the web interface to provide descriptive email alerts.

The on-board, easy to use embedded graphical user interface requires no software to maintain, and remote updates can be made over Ethernet.

Remote TCP/IP Monitoring & Control

TCP/IP remote management and power control of system and individual outputs

  • On-board web server means no software to maintain
  • Extremely easy to use Graphical User Interface
  • Remote firmware update capability
  • HTTPS, SMTP, SNMPv1/2c/3 protocols supported
  • Monitoring and alarm reporting of each output for pinpointing of issues with connected loads
  • Alarms can be sent to multiple email accounts
  • Each output has adjustable load-shed settings
  • Network Watchdog feature will ping a pre-determined I.P. address and power-cycle connected device if not answered
  • Five digital inputs for site monitoring sensors with email notifications sent
  • Data logging
  • Password protection

Standards 

MIL-STD-810G tested and verified for shock and vibration, salt fog, humidity, sand and dust, including Method 507.6

Procedure II Aggravated, Method 514.7 Procedure I Category 4, and Method 510.6 Procedure I Blowing Dust.

SPECIFICATIONS

SPECIFICATIONS
Application Voltage (pos or neg ground)12, 24, 48VDC
System Current Rating (peak/cont)200A/160A
Operating Voltage Range10-60VDC
Number of Outputs per bus6
Bus Current Rating (peak/cont)100A/80A
Number of Breaker Outputs12
Max Breaker Ratings (12,24V/48V)25A/15A(1)(2)
ENVIRONMENT
Operating Temperature Range -30 0C to +60 0C
STANDARDS (Tested and Verified for Military Use)
HumidityMIL-STD – 810G CHG 1 Method 507.6
Procedure II Aggravated
VibrationMIL-STD-810G CHG1 Method 514.7 Procedure
I Category 4, Composite Wheeled Vehicle
Blowing DustMIL-STD – 810G CHG 1 Method 510.6
Procedure I Blowing Dust
MECHANICAL
Dimensions (inches) L x W x H9.29 x 19.0 x 1.72
Weight (lbs/kg)7.0 lbs / 3.2 kg
ConnectorsM8 DC input stud connectors,
10-22AWG cage clamp output
terminal blocks
COMMUNICATIONS & CONTROL
EthernetTCP/IP built-in web server and graphical user interface, 10/100BASE-T, IEEE 802.3 compatible
Supported ProtocolsIPv4, HTTP, HTTPS, SMTP, DNS, TCP, UDP, ICMP, DHCP, ARP, SNMP v1/v2c/v3
SNMP PortsUDP Port 161, SNMP Traps: UDP Port 162
Firmware UpgradesUpgradeable over Ethernet
SecurityPassword protected, SSL encryption
12 Channel Output MonitoringCurrent draw measured and reported for each output, user definable under and over current alarms
Email and SMS AlertsMultiple email or text accounts, adjustable intervals
Data LoggingUp to 30 days at 1 minute sampling rate, csv file download, major event logging
Network WatchdogAutonomously ping up to two I.P. addresses and power-cycle output if no response, definable settings
Power Cycling and RebootingRemote on/off control of every output individually
Auto Restore ModeReturn to previous output settings after a power loss
Power-up Delay SequencingUser selectable 0 to 60 second delay between outputs
Auto Load SheddingEach output user definable, manual or auto restart

MODEL SERIES

INFORMATIONMODEL NO.
6/6 dual bus DC distribution panel, 200A system ratingICT200DB-12IRC/MIL
5 Amp hydraulic/magnetic circuit breakerICT-CB5 (1) (2)
10 Amp hydraulic/magnetic circuit breakerICT-CB10
15 Amp hydraulic/magnetic circuit breakerICT-CB15
25 Amp hydraulic/magnetic circuit breakerICT-CB25
Unused breaker position blanking plateICT-BLP
(1) Please follow all recommendations of the manufacturer. Fuses, breakers and wiring should be continuously operated at no more than 80% of their current rating.
(2) Hydraulic/magnetic breakers not included, must be ordered separately.