  • Backing-up both 230Vac & 110Vdc loads
  • Charging batteries
  • Peak Shaving
  • Modularity: from 2.7 kW to 2 MW
  • Performing constant power battery tests
  • Re-injecting power into the (miro)grid
  • Easy integration with 3rd party device (Modbus, SNMP and HTTP)  with Inview controllers

Description

Multidirectional Power Inverter

Modular UPS To Secure 230VAC & 110VDC Loads And Charge 110VDC Battery Bank

Sierra Multi-directional - Inverter - Converter Australia

Dual AC & DC Output Converter

Sierra 25 – 110/230 can be used as a UPS to secure AC & DC loads and charge the batteries. The 3 all bidirectional ports allow for multiple innovative applications such as grid reinjection, peak shavings, phase balancing or energy sharing through DC distribution, among many others.

By using several modules, we can offer solutions for three-phase (3x400Vac + N) infrastructures.

The module can be integrated in small or large cabinets to reach up to 2 MW. With our new Inview S monitoring, you can benefit from a unique experience.

The total output power per module is 2.7 kW, limited to 2.4 kW for each AC or DC port.

Sierra Multidirectional Power Inverter - Mountings - Rack Mount -Floor Mount

Monitor Unit – INVIEW S

nview S GUI Interface is a standard controller for ECI technology based bi-directional products. It is a powerful web-based touch screen graphical display, it allows user to easily access, monitor the system and protected with PIN code.In addition to the touch screen a web interface is accessible via ETH port.

  •  Measures: AC IN, AC OUT, DC, Module Information
  • 3 LED’s ( OK – Green, Minor Alarm – Orange, Major Alarm – Minor)
  • 2 outgoing alarm contacts (1 – Minor and 1 – Major)
  • 2 Digital Inputs
  • 2.8’’ touch screen
  • Web browser with laptop (ETH, SNMP, MQTT, Modbus, CAN,….)

Monitoring Inview User Manual

Inview 5 Controller for Modular Inverter and UPS Systems

Inview 5 – Smart Controller for Modular Inverters & UPS Systems

Additional information

NETWORK MANAGEMENT PROTOCOLS

Operating Modes

From The Grid

AC in feeds both <<AC loads>> and <<DC loads + battery>>

From  Batteries

AC in feeds both <<AC loads>> and/0r  <<DC loads + battery>>

Batteries AC loads and grid injections - Sierra biredirectionalFrom AC Loads

AC in feeds both <<AC loads>> and/0r  <<DC loads + battery>>

AC loads power by batteries

Monitoring Devices