48Vdc 1.25A 60W DIN Rail Power Supply / Battery Charger – ADC5823

Brand: Enedo

SKU: ADC5823
  • 48Vdc nominal output voltage (45-58Vdc adjustable output)
  • 1.25A output current (max)
  • 230/115Vac input voltage
  • Temperature compensated battery charging
  • Built-in output series diode
  • EMC EN55022B (telecom)

Datasheets

48Vdc 1.25A 60W DIN Rail Power Supply / Battery Charger – ADC5823

48Vdc 1.25A 60W DIN Rail Power Supply / Battery Charger – ADC5823

Description

Compact and stable DIN rail power supply / battery charger suitable for all types of industrial application. Very low ripple, built-in series diode and temperature regulated output voltage. LED indication for supply output voltage. Stable, mechanical construction, high efficiency, and convection cooling ensure long service life.

  • Input voltage 230/115 Vac / 85-200Vdc* (*not UL62368-1 approved)
  • Output voltage 48Vdc nominal output voltage (45-58Vdc adjustable output)
  • Output current 1.25A (max)
  • Efficiency 85%
  • Statistical MTBF >3 000 000 hours
  • Temperature-compensated battery charging
  • Operating temperature –40 °C…+70 °C (see derating)
  • EMC EN55022B (telecom)
  • Build-in series diode for floating output and redundant configuration

Specifications Table

 

Input
Input Voltage230Vac / 115Vac Selectable
85-200Vdc (not UL62368-1 approved)
Input Current at 100% Load2.5A (230Vac) / 4.5A (115Vac)
Input Frequency45-65Hz
Efficiency90% (typical 230Vac @ 100% Load)
IsolationInput/Ground: 1500Vac RMS 50Hz 1min
Input/Output: 3000Vac RMS 50Hz 1min
Output/Ground: 500Vdc
Inrush Current<35A <5ms (230Vac 25°C)
<17A <5ms (115Vac 25°C)
Input FuseT6.3A High Breaking
Overvoltage Transient ProtectionVDR 300VAC 77J
Output
Output Voltage48Vdc
Output Adjustement45-58Vdc
Ripple Voltage<15mVrms
Load Regulation<0.5% (without series diode)
Line Regulation<0.15% Uinmin – Uinmax
Temperature Coefficient<0.02% / °C
Current Limit<2A (refer current limiting curve)
Short Circuit Current<8A (refer current limiting curve)
Hold-up time>50ms (230Vac / 100% load)
Alarms and Indications
Output OKGreen LED
Power Fail Relay Alarm24VDC/0.3A / 30Vac/0.5A NO/NC relay contacts. Activated at AC fail and module fail cases. Galvanic reinforced isolation from the mains hazardous voltage required!
Under Voltage Alarm Threshold41V •2V
Output Overvoltage Protection61V
Optional ShutdownExternal voltage 4-15Vdc to RC pin
Optional Battery Test ControlFloat charge voltage can be reduced by external 4-15Vdc control to allow battery test by using external measurement circuit
Temprature CompensationExternal 2.2kΩ NTC resistor included.
No external voltage allowed!
Environmental
Storage Temperature-40°C – +85°C
Operating Temperature-40°C – +70°C (derating from 55°C, see curve). Maximum pollution degree 2 allowed.
CoolingNatural convection
Humidity85% RH

Do not energise while condensation present.

Shock and VibrationETS 300 019-2-4 class 4M5

Vibration sin IEC60068-2-6, 2gn, 9-200m/s2

Vibration broad-band random, IEC60068-2-64

Mechanical
Dimensions51(W) x 121(H) x 81(D)mm
Weight360g
EnclosureSteel / aluminium enclosure IP20
ConnectorsRemovable 2.5mm2 screw terminals
Standards & Approvals
Safety StandardsIEC62368-1:2018 National Difference: EU Group Differences, CA, US
EMC Emissions EN61000-6-3EN 55022 Class B
Conducted and Radiated EmissionsEN61000-3-3 Flickering
EMC Immunity EN61000-6-2EN 61000-4-2 Electrostatic Discharge

EN 61000-4-3 Radiated Immunity

EN 61000-4-4 Fast Transients

EN 61000-4-5 Surge

EN 61000-4-6 Conducted Immunity

EN 61000-4-8 Power Frequency Magnetic
Field Immunity

EN61000-4-11 Voltage Dips and
Inturreiptions Immunity

ApprovalsCE-marking, CE certificate IEC 62368-1:2018